• Power range 15KVA
  • 24V/48VDC input voltage
  • Powerful charge rate up to 65Amp
  • Inbuilt pure copper transformer
  • Pure sine wave output
  • LED+LCD display
  • MPPT solar charge controller 120A
  • MPPT efficiency max 98%
  • 50/60Hz automatic sensing
  • RS232 with free CD
  • Battery priority function
  • Automatically send signal to start generator
  • DC start & automatic self-diagnostic function
  • High efficiency design & “Power Saving Mode” to conserve energy
  • MODEL : PV35-15K Pro
    Default Battery System Voltage: 48VDC

    INVERTER OUTPUT
    Continuous output power : 15KVA/12.0KW
    Surge rating (20ms): 36.0KW
    Capable Of Starting Electric Motor: 6HP
    Output waveform : Pure sine wave/ same as input (bypass mode)
    Inverter Efficiency(Peak) : >88%
    Line mode efficiency : >95%
    Power factor : 1.0
    Nominal output voltage: RMS 220V/230V/240VAC(+/-10% RMS)
    Output frequency: 5OHz/60Hz +/-0.3 Hz
    Short circuit protection: Yes (1sec after fault)
    Typical transfer time: 10ms(max) 10ms(max)

    AC INPUT
    Voltage: 230VAC
    Selectable Voltage Range: 155~280VAC(For Personal Computers)
    Frequency Range: 50HZ/60HZ (Auto sensing) 40~80Hz

    BATTERY
    Minimum start voltage : 20.OVDC/21.0VDC for24VDC mode (40.OVDC/42.0VDC for 48VDC mode)
    Low battery alarm : 21.0VDC+/-0.3V for 24VDC mode (42.OVDC+/-0.6V for 48VDC mode)
    Low battery Cutoff : 20.0VDC+/-0.3V for 24VDC mode (40.OVDC+/-0.6V for 48VDC mode)
    High voltage alarm : 32.0VDC+/-0.3V for 24VDC mode (64.OVDC+/-0.6V for 48VDC mode)
    High battery voltage recover: 31.0VDC+/-0.3V for 24VDC mode (62.OVDC+/-0.6V for 48VDC mode)
    Idle consumption-search mode: 25W when power saver on

    CHARGER
    Output voltage : Depends on battery type
    Charger AC input breaker rating: 63A
    Max charge power rate: 1/3 Rating power
    Overcharge protection S.D.: 31.4VDC for 24VDC mode (62.8VDC for 48VDC mode )
    Maximum Charge Current: 100A

    BTS
    Continuous output power Yes Variances in charging voltage & S.D. voltage base on the battery temperature

    BYPASS & PROTECTION
    Input voltage waveform : Sine wave (grid or generator)
    Nominal voltage: 220V/230V/240VAC
    Max input AC voltage: 300VAC for 230VAC HV mode
    Nominal input frequency: 50Hz or 60Hz
    Overload protection (SMPS load): Circuit breaker
    Output short circuit protection: Circuit breaker
    Bypass breaker rating : 63A
    Max bypass current 80Amp
    Rated voltage: 24VDC/48VDC
    PV open circuit voltage: Operational max = 145VDC temperature corrected VOC

    SOLAR CHARGER
    Maximum PV Charge Current : 60A
    DC Voltage: 48V
    Maximum PV Array Power: 3200W
    MPPT Range @ Operating Voltage: 64~145VDC
    Maximum PV Array Open Circuit Voltage: 147VDC
    Maximum Efficiency: >98%
    Standby Power Consumption: 2W

    MECHANICAL SPECIFICATIONS
    Mounting : Wall mount
    Inverter dimensions (W*H*D): 587*414*211mm
    Inverter weight (solar chg) KG: 70+2.5
    Shipping dimensions(W*H*D): 750*520*310mm
    Shipping weight (solar chg) KG: 72+2.5

    OTHER
    Operation Temperature Range: 0�C to 40�C
    Storage Temperature: -15�C to 60�C
    Audible Noise: 60dB MAX